252(Solved): LIT Problem List: DTW-112,123,202
Posted on 16th May 2023, 9:12am by so@so.com
2023-05-23 04:00:05pm: Status changed to Pending, Because of: DTW112: Breakdown need for LIT installation.
DTW123: Up to 15 meters LIT goes down after then flexible pipe block.
DTW202: LIT need to check, Parvas will take care of this. -by: Zahid Hossain
2023-06-03 09:32:43am: Status changed to Solved, Because of: In dtw-202, I resetting the parameter of Level controller. Now LIT shows exact value. -by: Parves